Cross reference the distance from your pump to the electrical service entrance to determine the correct gauge. | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Motor Rating | Copper Wire Size | ||||||||||
HP | Wire Count | Phase | Volts | 12 Gauge | 10 Gauge | 8 Gauge | |||||
.5 HP | 3 Wire | 1 ∅ | 115V | 160 ft. | 255 ft. | 404 ft. | |||||
.5 HP | 3 Wire | 1 ∅ | 230V | 571 ft. | 912 ft. | 1444 ft. | |||||
.5 HP | 2 Wire | 1 ∅ | 115V | 178 ft. | 284 ft. | 449 ft. | |||||
.5 HP | 2 Wire | 1 ∅ | 230V | 742 ft. | 1183 ft. | 1874 ft. | |||||
.5 HP | 3 Wire | 3 ∅ | 230V | 1202 ft. | 1917 ft. | 3037 ft. | |||||
.75 HP | 3 Wire | 1 ∅ | 230V | 447 ft. | 713 ft. | 1129 ft. | |||||
.75 HP | 3 Wire | 3 ∅ | 230V | 894 ft. | 1426 ft. | 2258 ft. | |||||
.75 HP | 2 Wire | 1 ∅ | 230V | 562 ft. | 897 ft. | 1420 ft. | |||||
1 HP | 3 Wire | 1 ∅ | 230V | 371 ft. | 592 ft. | 937 ft. | |||||
1 HP | 3 Wire | 3 ∅ | 230V | 742 ft. | 1183 ft. | 1874 ft. | |||||
1 HP | 2 Wire | 1 ∅ | 230V | 430 ft. | 686 ft. | 1087 ft. | |||||
1.5 HP | 3 Wire | 1 ∅ | 230V | 320 ft. | 510 ft. | 808 ft. | |||||
1.5 HP | 3 Wire | 3 ∅ | 230V | 571 ft. | 912 ft. | 1444 ft. | |||||
1.5 HP | 2 Wire | 1 ∅ | 230V | 335 ft. | 535 ft. | 847 ft. | |||||
2 HP | 3 Wire | 1 ∅ | 230V | 286 ft. | 456 ft. | 722 ft. | |||||
2 HP | 3 Wire | 3 ∅ | 230V | 459 ft. | 732 ft. | 1159 ft. | |||||
3 HP | 3 Wire | 1 ∅ | 230V | 211 ft. | 337 ft. | 534 ft. | |||||
3 HP | 3 Wire | 3 ∅ | 230V | 345 ft. | 551 ft. | 872 ft. | |||||
5 HP | 3 Wire | 1 ∅ | 230V | N/A | 206 ft. | 326 ft. | |||||
5 HP | 3 Wire | 3 ∅ | 230V | N/A | 318 ft. | 503 ft. |